The service life of a water pump cannot be separated from regular inspections. The inspection process mainly judges the condition of the water pump through the external operating performance of the water pump, so as to find out the abnormality of the water pump. Most abnormalities are not irreversible damage to the water pump. If the fault can be diagnosed and maintained in the first time, the water pump can be restored to normal operation.
There are five main manifestations of water pump abnormalities: abnormal noise, abnormal vibration, abnormal performance, abnormal temperature rise, and other abnormalities
Most performance abnormalities are not found from the water pump itself, but are manifested through other upstream and downstream components of the water pump system, such as small water flow from the faucet at the end of the water pump system, high temperature and high pressure alarm of the upstream heat source host, poor heating effect of the downstream fan or floor heating, etc. For performance abnormalities monitored externally, the final manifestation is that the flow or head on the water pump does not meet the design. The reasons for this situation are usually:
The water pump is not exhausted
Exhaust is a necessary step for the initial installation of the water pump. Failure to exhaust or incomplete exhaust will cause the phenomenon of gas and water mixing in the pump body. When there is continuous gas in the pump body that cannot be discharged, it will cause the performance curve of the water pump to decay, and the flow rate and head to decrease.
When the pump is stopped, open the exhaust screw. If there is gas escaping, or gas escaping after filling with water, it can be determined that there is gas in the pump body. In this case, the pump should be completely exhausted or completely filled. After the pump body is filled with water, close the exhaust screw and run the water pump.
In some cases, there will be gas in the suction pipe of the water pump, and it takes multiple exhausts or fillings to solve the problem.

Cavitation
Cavitation has been mentioned in the previous content. In addition to causing vibration and noise in the water pump, cavitation will also affect the performance of the water pump. This is because during the cavitation process, the impeller suction port presents a state of gas-water mixture. The presence of bubbles causes the cross-sectional area of the inlet flow channel to decrease, causing the flow velocity in the local area to increase, generating vortices, and affecting the performance of the water pump.
Since the characteristics of cavitation change with the flow rate of the water pump, when the outlet valve is gradually closed, the difference between the measured performance of the water pump and the curve performance will narrow, until it is closed to a certain angle or fully closed, the water pump performance will be consistent with the curve. Cavitation can be judged with the help of the characteristic curve.
There are many ways to solve cavitation, but it is difficult to implement, such as reducing the medium temperature, increasing the inlet pipe diameter to reduce resistance, reducing the inlet pipe length to reduce resistance, and reducing the outlet valve opening.
Gas blockage

The problem of air blockage often occurs in sewage pump systems. When the sewage pump stops, the liquid level drops below the impeller. When the water comes back for the second time, the pump and the outlet pipeline are blocked by gas, causing the water level inside the pump body to be unable to rise to the height of the impeller. At this time, the pump will cause the impeller to be unable to contact the water and run idle.
In this case, the operating current of the water pump is small, and the problem of air blockage can be judged by the current.
To solve the air blockage, a vent hole needs to be opened on the pipe section from the outlet of the water pump to the check valve to discharge the gas inside the pump body.
Pump body air pocket
There are similarities between air trap in the pump body and unvented water pump, both of which are the phenomenon of air and water mixed in the pump body, but the key difference lies in the internal structure and installation angle of the pump body, which causes a part of the air in the pump body to always be unable to be discharged by filling the pump or exhausting the air. This can be analyzed and confirmed through the system structure.
When the water pump is in the pump body, it is necessary to change the installation angle of the water pump to make it correctly installed, so that the problem can be eliminated by exhausting or filling the pump.

Motor reverse

For three-phase motor water pumps, the motor direction is a place where errors are easy to occur. When the motor direction is not verified during debugging, the water pump may reverse, which will cause the water pump performance to decline sharply and fail to provide effective flow and head.
You can confirm whether the water pump is reversed by observing the motor direction. The correct direction can be checked from the external markings of the pump body, or identified by the appearance of the pump head and the impeller.
For the problem of motor reversal, you can swap the line sequence of any two phase lines to achieve it. If the water pump is driven by a frequency converter, changing the direction requires adjusting the wiring sequence between the motor and the frequency converter, or using the frequency converter parameter adjustment.
Impeller dropped
When water hammer occurs frequently in the system, the impeller may reverse and loosen, and eventually fall off. After the impeller falls off, the operation of the water pump will not be able to drive the impeller to work on the water, and naturally there will be no flow and head. At this time, the current of the motor is roughly the no-load current, and the current can be used to assist in judging this problem.
The repair of impeller falling off is relatively simple, just disassemble the pump body and reinstall it, but the key is how to determine the cause of the fall and avoid falling again.

System resistance does not match

In some systems, the performance of the water pump itself meets the design parameters, but the system cannot reach the design operating point when it is running. This problem may be in the system, not in the water pump. It may be caused by the system resistance deviating too much from the design operating point.
For example, the pipeline designed for a circulation system is too thin, and there are many elbow valves, resulting in a steep resistance curve. Even if the valve is fully opened, the pipeline resistance cannot be reduced, resulting in a water flow rate lower than the design value.
In this case, through the adjustment of the valve, it is found that the operating point of the water pump can only work on the left section of the curve. The system needs to be modified to reduce the system resistance to release the water pump flow.
Performance checkpoint error
In rare cases, the abnormal pump performance we see is not really abnormal, but may be a “misjudgment” caused by the wrong collection point for flow and head. This error mostly comes from the data feedback of the pressure gauge or pressure sensor. When we use the pressure gauge/pressure sensor at the wrong point, the pump head read may be consumed by resistance elements such as valves or check valves, which may be lower than the actual head of the pump.
It is necessary to determine whether there is an inaccurate head calculation problem based on the location of the system pressure point, and measure the pressure value near the pump inlet and outlet.

Controller settings error

Some water pumps with variable frequency control usually allow the setting of pressure or frequency to achieve energy-saving effect by reducing frequency. However, if the pressure or frequency is set too low, it may cause insufficient water discharge performance of the water pump. In this case, the problem can be solved by simply correctly setting the frequency converter.
Impeller assembly error
Impeller assembly errors are often seen after the pump is disassembled and maintained on site. The order of reinstalling the impeller is wrong, and the positioning sleeve is installed in the wrong position, resulting in axial movement of the impeller, damage to the structure of the mouth ring, and a large amount of backflow at the impeller suction port. The flow and head are lost, and the pump efficiency decreases. For this problem, it is necessary to disassemble the pump head and measure the impeller installation size for inspection. If it is indeed an installation error, it needs to be reinstalled.

Impeller damage
Due to long-term cavitation or foreign matter entering the pump body, the impeller is worn, and the blades and cover plates are damaged by lack of flesh and penetration, which will affect the hydraulic performance of the impeller and cause the attenuation of flow head. This kind of damage is difficult to judge from the outside, and the pump head needs to be disassembled to check the impeller.
For severely damaged impellers, they need to be replaced. Replacing the impeller is not difficult, but it is still necessary to check the cause of the impeller damage to avoid further damage later.
Regular inspections allow us to detect water pump abnormalities as early as possible, find the cause and deal with it in time to reduce costs. However, most people cannot accurately find the cause of water pump abnormalities, resulting in low efficiency or even damage to the water pump.